PRIMARY INJECTION TEST SYSTEM Raptor

Loading...

PRIMARY INJECTION TEST SYSTEM

Raptor

www.smcint.com

2

3

4

5

GENERAL

RAPTOR-MS

(values @240 Vac, 50 Hz, 1 sec. turn 960 mm2, measured 25 cm on each side) HIGH CURRENT OUTPUT

Master unit’s features Regulated high current output. Able to inject up to 3.8kA (with 3kVA) indefinitely or 9,5kA (with 2kVA) during 3s using a single turn In the case of being N turns the injecting current will be divided by N but power will be maintained. Each Slave unit adds nearly twice the power generated by the Master unit. These systems will be able to inject up to 15kA during 3s. Regulated auxiliary output. Working in current mode is capable of injecting up to 9 A indefinitely or 35A for 3s and it is regulated by primary. Working in Voltage mode is capable of generating voltage up to 200V Voltmeter Input. Ranges: 0.2, 2, 20 or 300Vac/dc (auto or manual). Built-in phase angle meter.

Supply

230 ±10%, 50/60 Hz

Weight

35 Kg

Protections

Protected by miniature circuit breaker

Output Current

Output Voltage

Sec. hole diameter

85 mm

No Load V (0%Imax)

0-1,20 Vac - Continuous

Transport

Wheels, folding handle, fixed handle

3,8 KAac (30%Imax)

0-0,81 Vac - Continuous

7,5 KAac (60%Imax)

0-0,42 Vac - 3 min

13 KAac (Imax)

0-0,22 Vac - 3 s

No Load Resolution

25 uVac

Output Frequency

20-400 Hz (Power reduction applied at 50 > f > 60 Hz)

Output Current

Output Voltage

LOW CURRENT OUTPUT

(Not simultaneous with high current output)

No Load V (0%Imax)

0, 0.79 or 1.59 Vac - Continuous

Output Current

0-35 Aac (0 – 9 Aac continuous)

3,8 KAac (25%Imax)

0, 0.67 or 1.34 Vac - Continuous

7,5 KAac (50%Imax)

0, 0.55 or 1.11 Vac - 3 min

15 KAac (100%Imax)

0, 0.30 or 0.61 Vac – 3 s

RAPTOR-SL

(values @240 Vac, 50 Hz, 1 sec.turn 960 mm2, measured 25 cm on each side) HIGH CURRENT OUTPUT

Voltage Output

0-200 Vac

Ammeter input. Ranges: 0.2, 2 or 20Aac/dc (auto or manual). Built-in phase angle meter.

Output Frequency

20-400 Hz (Power reduction applied at 50 > f > 60 Hz)

Low signal Voltmeter. Ranges: 30, 300 or 3000 mVac/dc (auto or manual). Built-in phase angle meter.

Isolated output

Yes

2 IrDA interfaces

Binary input. Voltage or dry contact

Protection

fuse

GENERAL

LEDs: Report on certain states of the unit: overload, temperature, status of communications, standby, digital input status indicators, power outputs and supplied unit status. IRDA interfaces: Connects Raptor-SL units, one with each other, and / or the Master Raptor-MS.

MEASUREMENTS

COMMUNICATIONS Two channels for master/slaves linking

Supply

230 ±10%, 50/60 Hz

(for high current output)

Weight

35 kg

Ranges

0-1 / 0-15 KAac

Protections

Protected by miniature circuit breaker

Resolution

1 Aac, 10 Aac

Sec. hole diameter

85 mm

Accuracy

±0,2% of the value ±0,2% of the range

Transport

Wheels, folding handle, fixed handle

Phase angle

±0,25º

Secondary Current

Ammeter/Low Level Voltmeter Amm. Ranges

0-0,2 /0-2/0-20 Aac

RAPTOR-HH

Amm.Resolution

0,1 mAac, 1 mAac, 10 mAac

CONTROL

Amm. Impedance

<10 mΩ

Volt. Ranges

0-30 mVac,0- 0,3 Vac, 0- 3 Vac

Volt. Resolution

Display

Transflective high definition color TFT with resistive Touch Panel, 54x71 mm (5,7”)

0,015 mVac, 0,15 mVac, 1,5 mVac

Wheel

Rotary Encoder (Wheel and click)

Volt. Impedance

>3000 KΩ

LEDs

Alarm, Connectivity, Power

Frequency range

20-400 Hz

COMMUNICATIONS

Accuracy

±0,1% of the value ±0,1% of the range

RS-485

RAPTOR BUS Communication with RAPTOR-MS

Phase angle

±0,25º

USB

Connection to PC (RAPTORSync)

Isolated input

Yes

RJ-45

Ethernet for software updates Mini-PC powered by Windows CE

Voltmeter Ranges

0-0,2/0-2/0-20/0-300 Vac

GENERAL

Resolution

0,1 mVac, 1 mVac, 10 mVac, 0,15 Vac

Power Supply

Impedance

>120 KΩ

Self-powered from RAPTOR-MS, or with external power adapter 5 Vdc

Frequency range

20-400 Hz

Weight

0,4 Kg

Accuracy

±0,1% of the value ±0,1% of the range

Dimensions

110 x 185 x 35 mm

Phase angle

±0,25º

Case

Isolated input

Yes

High quality injection-moulded ABS, strong and ergonomic design, edge surfaces protected with TPE non-slip material

Compliance

The instrument is intended for use in high-voltage substations and industrial environments. All EuroSMC products have conformity to CEmarking directives, complies with IEC and international standards, and are designed and manufactured in accordance with the requirements of the ISO-9001 Quality Standard

Transport Bag

Nylon soft bag

Connection cable

5 m cable, 8 mm

Binary Input Type

Dry contact/Voltage

Voltage mode Levels

1,5 V , 15 V

Time resolution

1 ms

Max. Voltage

250 Vac

Isolated input

Yes

COMMUNICATIONS

6

2 RS-485

Raptor Bus connectors to control unit RAPTOR-HH and/or other units

2 IrDA interfaces

Two channels for master/slaves linking

7

Nº sec. turns

Compliance Voltage (V) RAPTOR-05

Compliance Voltage (V) RAPTOR-15

Compliance Voltage (V) RAPTOR-25

Compliance Voltage (V) RAPTOR-35

Max. Current (A) Continuous

Max. Current (A) 3 minutes

Max.Current (A) 3 seconds

1

0,81-(0,22)

2,15-0,26

3,50-0,87

4,84-1,48

3.800 @ 0,81/2,15/3,50/4,84 V

7.500 @ 0,42/1,53/2,63/3,73 V

(9.500) 15.000 @ (0,22)/0,26/0,87/1,48 V

2

1,61-(0,33)

4,30-0,52

6,99-1,73

9,68-2,95

1.900 @1,61/4,30/6,99/9,68 V

3.800 @0,83/3,02/5,21/7,40 V

(5.000) 7.500 @(0,33)/0,52/1,73/2,95 V

3

2,42-(0,06)

6,45-0,77

10,49-2,60

14,52-4,43

1.267 @2,42/6,45/10,49/14,52 V

2.500 @1,27/4,58/7,88/11,19 V

(3.800) 5.000 @(0,06)/0,77/2,60/4,43 V

4

3,23-(0,66)

8,61-0,90

13,98-3,28

19,36-5,66

950 @3,23/8,61/13,98/19,36 V

1.900 @1,66/6,04/10,42/14,79 V

(2.500) 3.800 @(0,66)/0,90/3,28/5,66 V

5

4,04-(1,09)

10,76-1,29

17,48-4,34

24,20-7,38

760 @4,04/10,76/17,48/24,20 V

1.500 @2,12/7,63/13,14/18,64 V

(1.900) 3.000 @(1,09)/1,29/4,34/7,38 V

OPTIONAL ACCESSORIES

ORDERING INFORMATION SYSTEM CONFIGURATION RAPTOR - 05

1 x Raptor-HH + 1 x Raptor-MS

RAPTOR - 15

1 x Raptor-HH + 1 x Raptor-MS + 1 x Raptor-SL

RAPTOR - 25

1 x Raptor-HH + 1 x Raptor-MS + 2 x Raptor-SL

RAPTOR - 35

1 x Raptor-HH + 1 x Raptor-MS + 3 x Raptor-SL

CBL3M-RAP

120 mm2 cross section and 3 meters (9 ft) long

CBL6M-RAP

120 mm2 cross section and 6 meters (18 ft) long

CBL9M-RAP

120 mm2 cross section and 9 meters (27 ft) long

RAP- ACC1

Up to 4 CBL cables can be connected

RAP- ACC2

Up to 6 CBL cables can be connected

ACCESSORIES INCLUDED RAPTOR-HH Hand held console with software Stylus Nylon Bag System cable USB cable Ethernet cable Power adapter User’s Manual RAPTOR-MS Raptor master unit Power supply cord Low signal voltmeter cable Calibration certificate Nylon protective bag RAPTOR-SL Raptor slave unit Power supply cord Nylon protective bag

European Office EuroSMC S.A

LATIN AMERICA Office

Polígono Industrial P-29 - c/ Buril 69 28400 Collado Villalba -Madrid -Spain Tel: (+34) 918498980 Fax: (+34) 918512553

USA Office NoramSMC Inc.

5840 South Memorial Drive - Suite 208 Tulsa - OK 74145 - USA Tel: 1 918 622 5725 Fax: 1 918 664 2073

Monte Rosa 255 4to Piso Chacarilla - Surco Lima, PERU Tel.: +511 625 9765 Fax: +511 638 1919

Unit B, 7/F, Southgate Commercial Centre, 29 Granville Rd, Tsim Sha Tsui, Kowloon, Hong Kong SAR. Tel: +852 3590 2499 Fax: +852 8343 0198

[email protected] www.smcint.com

[email protected] www.noramsmc.com

[email protected]

[email protected]

8

ASIAN Office

Loading...

PRIMARY INJECTION TEST SYSTEM Raptor

PRIMARY INJECTION TEST SYSTEM Raptor www.smcint.com 2 3 4 5 GENERAL RAPTOR-MS (values @240 Vac, 50 Hz, 1 sec. turn 960 mm2, measured 25 cm...

3MB Sizes 2 Downloads 7 Views

Recommend Documents

PRIMARY INJECTION TEST SYSTEM Raptor - Advanced Test
Raptor system includes factory configured tests, to automatically perform a large amount of the most common testing, ...

PRIMARY INJECTION TEST SYSTEM Raptor - Alphatech
the entire circuit; current transformer primary and secondary windings, relays, trip and alarm circuits, circuit breaker

INGVAR Primary Current Injection Test System - intyler fimaco
This powerful test system is designed for primary injection testing of protective relay ... Burden of secondary circuits

Programma ODEN AT Primary Current Injection Test System - Surgetek
Primary current injection testing and breaker testing. These tests require high ... as the nominal value (1000/5 for exa

ODEN AT Primary Current Injection Test System - STEVO Electric
This powerful test system is designed for primary injection testing of protective relay equipment and circuit breakers.

2 Primary Current Injection Test Sets
circuit means that the method is unsuitable for routine testing. For routine testing secondary current injection testing

2 Primary Current Injection Test Sets - Test-Meter.co.uk
circuit means that the method is unsuitable for routine testing. Secondary Injection Testing. Secondary current injectio

Magnetization and Primary Injection Test of Current Transformer for
injection test of current transformer; a basic requirement to ensure that a ... primary (power) circuit and provide quan

Test & measurement - A primary injection primer - Electrical Review
Feb 4, 2011 - This is secondary current injection testing and it is widely used, not least because much lower currents a

Secondary Injection Testing vs. Primary Injection Testing for Circuit
Secondary injection testing: Can be done on Electronic breakers only; Quick; Tests the trip unit only; Easier; Takes les